Leaking Manufactured Stone & Leaking Windows Halt Progress on Custom Built Home

ACMV Part 3- Wall Details and Drainage

Start Here to read the first post in this series. This will help you better understand the details for each section of the ACMV series.

As I said before, flat walls are as easy as it gets when it comes to installing manufactured stone.  You really have to try to mess up an open wall, but you know what they say: where there is a will there is a way.  The MVMA guide doesn’t say a lot about how to treat large open spans of walls.  My guess is that this is because if you install the two layers of weather barrier, and do good job on your mortar bed, things should stay dry. But once you reach a corner (inside or out), then you have to follow some rules. These rules are simple, yet I still find the work done incorrectly. Sometimes I think these installers are doing it wrong on purpose.

Walls and Corners

If your install of manufactured stone wraps an outside corner, you are to use pre-made corner pieces first, and run those up the outside corners.  You then use the flat pieces to fill in the middle of the wall. This keeps the delicate outside corner covered and sealed, and it just looks better. Here is a picture of what the corner pieces look like before they are installed on the house.Outside Corner of Manufactured Stone

 

MVMA outside corner

The MVMA install guide gives us an overhead view of what the outside corner should look like.

 

As I said before, sometimes it’s as if the contractors do things wrong intentionally; although deep down I know it’s because they either just don’t care or just don’t know. Here is a corner where the installer simply ran flat pieces up to the edge of a corner when they got low enough you couldn’t see it from the ground (these shots were taken on the roof.)  You can clearly see the seam that it leaves exposed. What makes this particular install especially poor is that they did a shoddy job of wrapping the WRB (weather resistant barrier), and you can see the raw OSB plywood behind the stone. It is simply a matter of time before the walls of this house rot away.

Manufactured Stone Corner Detail

Here you can see what happens when the correct corner pieces are not used. It creates a vertical seam in the wall.  This not only looks terrible,  it creates a gap for water to get to the wood structure behind it.

 

Clearances and Drainage

Let us beat the proverbial dead horse, shall we? What you must keep in mind about stone siding:  It is not a question of if water will get in, but a question of how much water will penetrate behind the surface. Water soaks through the stone veneer itself; it wicks in around the cracks, it gets beamed through by Scotty…well maybe not that.  The point is, you can’t stop it. You can only control it. There must be a way for this water to escape in the form of natural drainage. This also means there must be clearances where the stone meets another surface (like front porches, roofs, sidewalks, etc.) to give this water a place to run to, and evaporate.  If we look back to our old friend, the MVMA guide, it tells us we should have several inches of clearance at the base of walls, around porches, and on top of shingles (hard surfaces), and a 4″ gap at dirt/grass/mulch.

Every place that concrete stone veneer touches another surface, there should be a drainage gap.

Now, I get it. The gap doesn’t look great from an aesthetics standpoint. But do you want a small gap in the stone at the base of your wall, or do you want rotting walls behind your stone?  Here is the detail from the MVMA guide on what the base of the walls should look like.  The areas that have been highlighted in red are the pieces that are, in my experience, always left out.

Foundation Wall Stone Veneer Detail

The MVMA guide says to keep a 2″ gap at the base of walls on paved surfaces, and a 4″ gap earth.

 

Now check out what I see in the real world. The manufactured stone is ALWAYS touching the porch and sidewalks. It is always buried in the mulch (or grass). In fact, I have never seen this detail correctly installed around the base of the wall. Here is a collage of images from homes that all have the same problem. No drainage behind the manufactured stone. No place for the water to escape.

Manufactured-Stone-Wall-Examples

The base of a wall should have a gap at the ground where the weep screed is allowed to drain moisture. That detail seems to be missing from every home.

 

Manufactured Stone No Weep Screed

Here is an example of a front porch that has the stone veneer installed on top of the concrete. No drainage. No weep screed.

 

Missing Weep Screed Wood Rot

This image from taken from the basement looking up at the damage caused by a botched installation of manufactured stone.

 

Dormers and Roofs

The roof line is another problematic spot where massive amounts of water are intermittently present. If the rules aren’t followed in this area, the exposure of the manufactured stone to all of that water will most certainly cause issues at some point. Much like their guidelines for stone near the ground, the MVMA recommends leaving several inches of clearance around the roof line. This area can get tricky, because a correct install here requires that both the siding contractor, and the roofer know what they are doing, that they communicate with each other. Most of time these folks are not on the job site at the same time, so how effective do you think they are about relaying information between them?  Here is a colored image from the MVMA guide so you can understand better what things should look like, followed by what I see in the field.

Manufactured-Stone-Sidewall-Roof

This detail from the MVMA is one of the harder ones to wrap your head around.  I’ve color coded the different parts to make it easier for you to see the layers, and what order they should be installed in.

 

Manufactured Stone Dormer Installation

Every important detail was skipped on this dormer and it leaked into the home, badly. This house was only two years old.

 

Manufactured Stone Dormer Installation Water Damage

Here you can see what a few years of water exposure will do to manufactured stone. The entire bottom edge is saturated with moisture.

 

Final Thoughts

Back in the 80’s and 90’s there was an extremely popular siding known as EIFS (Exterior Insulation Finishing System), also known as synthetic stucco. It was primarily installed on higher end homes. The installers back then ignored the rules and didn’t follow the instructions when it came to drainage and details around windows/doors/etc.  It didn’t take long before EIFS problems turned into an epidemic in just about every area of the country.  The water got in, and got trapped. Houses rotted from the inside, lawsuits started flying, and an overall good product like EIFS got a black eye. After all, when installed correctly, EIFS performs great.  The problem was not the product; it was the installers using it who didn’t read the instructions, and everything fell apart just a few short years later.

Fast forward 20 years.  History repeats itself.

Now there is a new synthetic siding on the market.  One that is failing when not installed correctly.  A siding that is trapping water and rotting homes.  A siding in which the details are being ignored by the installers.  The BIG difference between manufactured stone veneer and EIFS as I’m seeing it is that while EIFS was primarily installed on high-end homes, manufactured stone veneer is being installed on starter homes, mansions and everything in between. So when the lawsuits start flying this time, manufactured stone is going to make the EIFS problems look like the common cold compared to the Bubonic Plague.

If you have Manufactured Stone Veneer Siding (ACMV) on your home, I strongly suggest you get it checked out.  Research and locate a highly qualified home inspector or find a moisture intrusion expert contractor.

The ACMV diagrams from this series were all taken from the MVMA guide. I will sometimes remove extra details or color certain sections to make them a bit easier to understand. If you want to look at the originals, download the full MVMA manual.

 

 

ACMV Part 2- Trouble Areas Around Windows & Doors

Start Here to read the first post in this series. This will help you better understand the details for each section of the ACMV series.

If there is one constant when it comes to ACMV (Adhered Concrete Masonry Veneer), it is that you must be sure the moisture can drain from behind the siding. This drainage is achieved by incorporating a drainage plane & weep screed (a place for the water to drain to, and path for it to escape). When you look at all of the detailed diagrams on the subject, you’ll notice that every one of them has a drainage point where the siding meets another horizontal surface. This means that every window, door, trim piece, and the ground must have a drainage point to release the water that will get behind the siding.  If this detail is omitted, and it almost always is, moisture can build up and leak behind the moisture barriers that are in place.  Let’s look at some pictures to see what happens when things go wrong.

Window and Door Heading Detail

Below is a detailed diagram of what you should see when looking at ACMV manufactured stone install.  Notice the weep screed at the top of the window to give the moisture a place to drain, and an expansion gap (with backer rod and sealant to keep wind-driven rain out). When that flashing is missing (and it almost always is), the water that gets behind the stone will collect and build up on top of the window (the head).  I’ve added some rain drops to the image to help you better understand what happens to the moisture, and what path the water takes as the wall takes on wind-driven rain.

ACMV Window-Head-Detail

Here is a colored detail of what the top of a window or door should look like when looking at an ACMV install.

 

Now let’s look at a picture from an inspection of a typical ACMV install I see in Louisville during inspections. You’ll notice that the mortar was installed around the stones and it was also laid directly next to the window frame. The is no form of expansion gap, and the weep screed is missing.  Every important detail was skipped.

ACMV Failed Window Install

Here you can see the stone and mortar butted to the window. This will crack out over time and allow water to seep in around the window.

Window and Door Jam Details

The sides of windows call for the same backer-rod and sealant as the top, to allow for thermal movement. Remember from science class that almost everything expands and contracts when it heats up and cools down. We must allow for this movement, and flexible sealants are the best way to do so. We incorporate bond breakers like backer-rods  to help cut down on the amount of sealant used, and to keep the bond in the joint even.  I drew a couple of diagrams to help you visualize what the backer-rod/sealant joint would look like.

Backer-rod ACMV Control Joint

Here is an example of a properly sealed joint using backer-rod. This will expand and contract with thermal movement and keep things water tight.

 

Let’s look at a detail where the backer-rod is missing from the equation. When you don’t utilize a backer-rod, the sealant will flow and move inside the joint and grab more of one side than the other.  Think of this as a game of tug-of-war. One side has 10 people, one has 3 people. Who’s going to win? When one side is stronger than the other, the joint will fail and pull apart. This is what happens when you see a caulked joint that has cracked and opened up.

Sealant Missing Backer-rod

Here you can see what happens to the sealant when the backer-rod is omitted. The left side is going to win every time.

 

Here is what a typical install of ACMV around windows looks like in my area.  I’ve never seen an installer use backer-rod and sealant. It’s always either mortared straight to the window jam, or “dry stacked.” Both are a recipe for failure.  You know the old saying, “If you fail to plan, you plan to fail.”

ACMV Window Jam Failed Install

Here is what the sides of a window install will look like with the backer-rod and sealant missing. The mortar is installed right up to the jam.

 

Window Sills

One of the most important details with a waterproof installation of ACMV on your home should happen long before the stone veneer is ever installed. The opening for the windows must be wrapped in sill flashing.  This is usually done with a peel and stick product such as Grace Vycor Flashing.  If this step is omitted, compounded with the other skipped details, you will be left with water that will seep in around the corners of the window sills, and rot out the wall.  How fast this happens all depends on how much water gets in.

 

ACMV-Window-Sill-Detail

Window sills are treated like the sides of the window. There should be a 3/8″ gap between the faux stone and the window. The gap gets the backer-rod sealant to keep water out.

 

Leaking Window ACMV

This home had failure at the window corner. This picture was taken during the exploratory phase of the repair.

 

ACMV soaking up moisture

This window is missing the sloped sill material. It was also never caulked around the window jam. Notice how the bottom right corner is much darker than the rest of the wall. That is because it’s taking in water here and stays wet.

Identifying A Problem

Even though I have never seen an installation of ACMV that I would consider correct, I have seen several houses that are not showing signs of problems (to the naked eye).  Sometimes it take the Perfect Storm of circumstances before real problems pop up.  Sometimes it takes the right amount of rain exposure.  Sometimes enough time hasn’t elapsed for a water problem to manifest itself on the surface.

When I can’t simply look at the home and know there is an issue, I use technology to help out.

Moisture Meters- I carry several different kinds of moisture meters.  Each tool does one particular job well, and the specific task dictates which one I reach for.   When dealing with ACMV and windows, I use my GE Protimeter with deep wall probes.  Yes, it’s expensive, but it’s a drop in the bucket to what the repair costs on your house will be.

Your wall cavity is about 4″ thick.  Most of the time, the moisture will take years and years to show up on the inside of the home near the drywall.  However, using the wall probes, I’m able to take moisture readings through the 4″ of wall cavity and reach the backside of the substrate (the OSB plywood on the outside).  This surface is what the ACMV is actually mounted to.  If water is leaking in, the meter should find it.

To use the probes, I first drill two small holes in the drywall. Sometimes we get lucky and find an electrical outlet near the bottom of the window. When that happens, we can remove the cover plate and slide the probes between the electrical box and the cutout of the drywall. This keeps me from having to drill holes in the wall.

ACMV Deep Wall Moisture Scan

Once you drill two small holes in the drywall, the probes can be pushed through the wall cavity to take a moisture level reading while doing minimum damage to the wall.

 

As with other claddings used in construction, the details around doors and windows are what must be perfectly executed.  Flat walls are relatively easy; it’s when a change shows up in the  architecture that builders and contractors must follow details, or things go south in a hurry.  If you’ve compared your home to what I have detailed here and you’re concerned, I encourage you to reach out to a moisture intrusion expert to have your home examined.  If you are in my area, Louisville, KY, please feel free to contact me about getting your ACMV Inspection.

PART 3: ACMV- WALL DETAILS AND DRAINAGE

In part three I show you how the details around the walls should be handled, and how to make sure the water doesn’t build up behind the stone veneer.

The ACMV diagrams from this series were all taken from the MVMA guide. I will sometimes remove extra details or color certain sections to make them a bit easier to understand. If you want to look at the originals, download the full MVMA manual.